The ACD-102 pressure transmitter (backup battery) is a combination of our company's digital pressure transmitter technology features, with an added built-in battery, allowing the transmitter to perform pressure detection even without external power. The transmitter not only has the (4-20) mA analog signal output function of the transmitter, but also optional RS485 digital communication function and (5-30) Hz function; It has a rare five digit LCD backlight display for pressure transmitters.
Display Unit | Pa , kPa , MPa , psi , bar , mbar , kgf/cm2 , inH2O , mmH2O, inHg, mmHg |
Measurement Range | Gauge pressure: -0.1MPa~0~260MPa |
Accuracy | 0.05% / 0.1% / 0.2% / 0.5% |
Stability | Better than 15 years ± 0.2% URL |
Output | (4-20) mA (24V DC, two-wire system) (5-30) Hz pulse (5V DC, three wire system) |
Communication | RS485 (compatible with both Modbus RTU and ANCN Free Protocol) |
Power Supply | Internal power: 3.6V industrial lithium battery; (EMC characteristics of built-in battery are limited) ACD-102D: (4.5-36) VDC (24V typical) or 5V DC |
| Sampling Frequency | Internal power: (1-20) seconds/time, default 4 seconds/time, time can be set independently |
Ambient Temperature | (-30 ~ 85)℃ w/o LCD (-30~80) ℃ w/ LCD |
Relative Humidity | < 90% |
Atmospheric Pressure | (86~106)kPa |
Other | Calibrate the reference environment temperature: 20℃±2℃ |
| Process Temperature | Standard (-40~120) ℃ Wide-range (-60~150) ℃ |
Display | Five digit backlit display+percentage bar chart |
Protection Rating | IP65 |
Explosion-proof Rating | Ex d IIB T6 Gb |
Overload | 1.5 to 3 times the measuring range, depending on the measurement range |
Software Configuration | AncnView-TIntelligent instrument detection software (with RS485 communication): Real time display of instrument data, automatic recording, automatic drawing of pressure curves, can be exported to Excel spreadsheets for reading, printing and saving. |
Process Connection | M20x1.5 / M14x1.5 / M14x1, etc. G1/2 / G3/4 / G1/8 / G3/8 NPT1/2 / NPT1/4 / NPT 1/8, etc |